Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual

This is a user manual for MRR1 multifunctional generator rotor protection relay, which introduces the features and usage methods of the product


Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual - cover page
Brand
Woodward
Category
RELAY
Document type
User Manual
Language
English
Pages
24
File format
PDF
File size
643 KB
Published
03 November, 2023
Updated
03 November, 2023
Model
MRR1
MD5 checksum
33F25AEDE66A6854D54352A142EB0816

About this manual

The MRR1 is a multifunctional generator rotor protection relay from Woodward. It combines rotor earth fault protection, excitation over- and undercurrent protection, and rotating diode failure protection, and is recommended for synchronous generators and motors above 1 MVA rating. The manual lists the covered ANSI codes and describes the relay's features, connections, display, LEDs, and working principle.

The document explains operation and settings, including pickup values, tripping delays, slave address setting, reset, blocking of protective functions, and output relay assignment. It also covers relay testing and commissioning with power-on checks, output relay tests, secondary and real injection tests, maintenance, technical data, setting ranges, and an order form.

What's inside

  • Introduction and application
  • Features and characteristics
  • Design
  • Working principle
  • Rotor earth fault protection
  • Excitation current supervision
  • Operation and settings
  • Relay testing and commissioning
  • Technical data
  • Order Form

Specifications

Measuring frequency0.51 Hz
Maximum continuous current20 A DC
Nominal current10 A DC
Current circuit power consumption<1 VA
Dropout to pickup ratio>98%
Returning time≤30 ms
Minimum operating time≤100 ms
Temperature influence±2.5% at -20°C up to 70°C
Insulation test voltage2 kV DC for terminals A2/A3/A4 to earth (C9)
Number of output relays5

Frequently asked questions

What protective functions does the MRR1 combine?

The MRR1 combines rotor earth fault protection, excitation over- and undercurrent protection, and rotating diode failure protection.

What test frequency does the earth fault protection use?

It uses a test frequency of 0.5 Hz for detecting high impedance earth faults.

What is the exciter current measuring range?

The exciter current is measured via a Hall transducer with a measuring range of 0 to 20 A.

How many output relays does the MRR1 have?

It has 5 output relays; relays 1 to 4 are programmable, and relay 5 indicates self-supervision.