Woodward MRR1 Manuals

ManualLib has 2 documents for the Woodward MRR1 (RELAY): 1 user manual. Every file can be read online or downloaded as a PDF for free.

User Manual 1

Key facts

Model
MRR1
Category
RELAY
Documents
2
Languages
EN
Last added
2023-11-03

Start here

Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual

Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual

User Manual 24 pages · 643 KB · EN

The MRR1 is a multifunctional generator rotor protection relay from Woodward. It combines rotor earth fault protection, excitation over- and undercurrent protection, and rotating diode failure protection, and is recommended for synchronous generators and motors above 1 MVA rating. The manual lists the covered ANSI codes and describes the relay's features, connections, display, LEDs, and working principle.

The document explains operation and settings, including pickup values, tripping delays, slave address setting, reset, blocking of protective functions, and output relay assignment. It also covers relay testing and commissioning with power-on checks, output relay tests, secondary and real injection tests, maintenance, technical data, setting ranges, and an order form.

Read online

Woodward MRR1 specifications

Measuring frequency0.51 Hz
Maximum continuous current20 A DC
Nominal current10 A DC
Current circuit power consumption<1 VA
Dropout to pickup ratio>98%
Returning time≤30 ms
Minimum operating time≤100 ms
Temperature influence±2.5% at -20°C up to 70°C
Insulation test voltage2 kV DC for terminals A2/A3/A4 to earth (C9)
Number of output relays5

Source: Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual

All Woodward MRR1 documents by type

User Manual 1

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What protective functions does the MRR1 combine?

The MRR1 combines rotor earth fault protection, excitation over- and undercurrent protection, and rotating diode failure protection.

From: Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual

What test frequency does the earth fault protection use?

It uses a test frequency of 0.5 Hz for detecting high impedance earth faults.

From: Woodward MRR1 Multifunctional Generator Rotor Protection Relay User Manual