Woodward EGCP-3 LS Multi-unit Load Share Generator System Control Package Product Specification

Product specification for the Woodward EGCP-3 LS, a microprocessor-based generator system control package for engine, generator, and power system management.


Woodward EGCP-3 LS Multi-unit Load Share Generator System Control Package Product Specification - cover page
Brand
Woodward
Category
Generator
Document type
Product Leaflet
Language
English
Pages
4
File format
PDF
File size
212 KB
Published
12 October, 2026
Updated
12 October, 2026
MD5 checksum
9C5215C2BC396C3425454C5BC4791C05

About this manual

The EGCP-3 LS is a microprocessor-based generator system control and management package designed for demanding power generation applications. It integrates engine, generator, power system, switchgear, bus, and generator monitoring, protection, and control functions in a single, compact, and cost-effective package. The unit is suitable for medium and large-sized generation systems and can be operated alone or networked with other LS units or EGCP-3 MC units.

What's inside

  • Description
  • Applications
  • Real kW Load Control
  • Reactive kVAR Control
  • Engine Control/Protection
  • Automatic Unit Sequencing
  • Synchronizing
  • Communications
  • Diagnostic Features
  • Bus Protective Features

Specifications

Size282 mm (11.1") high x 358 mm (14.1") wide x 134 mm (5.275") deep
Operator Interface8 (20 character) lines plus membrane keypad
Power Supply Voltage24 Vdc system (18–32 Vdc nominal; 9–40 Vdc maximum)
Operating Temperature Range–20 to +70 °C (–4 to +158 °F)
Storage Temperature Range–30 to +80 °C (–22 to +176 °F)
Humidity95% at 60 °C non-condensing
Enclosure RatingType 4 (NEMA)
Voltage Measuring Input Range70–300 Vac
Current Measuring Inputs5 Aac RMS nominal, 7 Aac RMS maximum
Rated short-time current (1 sec)10 X (I) rated (8406-113 Rev E or later)

Frequently asked questions

What systems is the EGCP-3 LS designed for?

It is designed for use in stand-alone, peaking, or utility paralleled systems.

How many EGCP-3 LS units can be used for isochronous load sharing?

Up to 16 EGCP-3 LS units can be used for isochronous load sharing.

What communication networks does the EGCP-3 LS support?

It supports Modbus RTU via RS-232/-422/-485 serial ports, ServLink, Watch Window, and Echelon TP/XF-1250 network (LON).

Is the EGCP-3 LS compatible with DSLC units?

It is DSLC compatible, but not compatible with manually bound DSLC units.