This document provides descriptions and procedures for the Quick Installation of Honeywell’s ST 700 Basic SmartLine Pressure Transmitter.
Honeywell ST 700 Basic SmartLine pressure transmitters are available for differential, gauge, and absolute pressure measurement. This quick start guide covers installation tasks such as mounting, conduit entries, wiring and power-up, trimming, jumper settings, and basic configuration.
It describes bracket, flange, flush, and remote seal mounting options, housing rotation, leveling for small spans, failsafe and write-protect jumpers, and the standard display menu.
| Mounting pipe size | 2-inch (50 millimeter) vertical or horizontal pipe |
|---|---|
| Housing rotation | Maximum 180 degree increment |
| Set screw torque | 1.46 to 1.68 Nm (13 to 15 lb-in) |
| Flush mount locking bolt torque | 6.4 Nm ±0.30 Nm (4.7 ft-lbs ±0.2 ft-lbs) |
| Remote seal capillary head effect limit | 9 psi (300 mm Hg) absolute |
| Failsafe up-scale loop current | Greater than 21.5 mA |
| Failsafe down-scale loop current | Less than 3.6 mA |
| Standard display | 2 lines, 6 characters |
| Flush mount process connection | 1-inch standard pipe and one-inch weld nipple |
| Sanitary remote seal minimum capillary length | 1.5 m (5 ft) |
The housing can be rotated in a maximum of 180 degree increment left or right from center.
The default setting is up-scale failsafe.
Changed configuration parameters cannot be written to the transmitter.
Tighten the bolt to a torque of 6.4 Nm ±0.30 Nm [4.7 ft-lbs ±0.2 ft-lbs].