EATON Bussmann series photovoltaic application guide introduces the safety protection technology of photovoltaic system, including the construction of photovoltaic modules, current protection and voltage protection.
This guide explains photovoltaic module construction, string and array protection, and how to select fuse links for PV installations. It covers fuse selection criteria, worked examples, and an overview of Bussmann series solar fuse links and holders.
The guide states that Eaton Bussmann series PV fuse links are designed for IEC 60269-6 gPV protection, operate at 1.35 x In, and meet UL 2579. It also describes temperature derating for string fuse links and altitude derating above 2000 metres.
| PV fuse link operation | 1.35 x In |
|---|---|
| String fuse voltage rating | >= 1.20 x Voc x Ns |
| String fuse current rating | >= 1.56 x Isc |
| Altitude derating | 0.5% per 100 m above 2000 m |
PV systems with three or more strings connected in parallel need to have each string protected.
The fuse link voltage rating should be at least 1.20 x Voc x Ns.
The fuse link current rating should be at least 1.56 x Isc.
Above 2000 metres sea level, every 100 metre increase derates the fuse current by 0.5%.