Eaton Bussmann Series Photovoltaic Application Guide

EATON Bussmann series photovoltaic application guide introduces the safety protection technology of photovoltaic system, including the construction of photovoltaic modules, current protection and voltage protection.


Eaton Bussmann Series Photovoltaic Application Guide - cover page
Brand
Eaton
Category
Other Electronics
Document type
Application Note
Language
English
Pages
72
File format
PDF
File size
2.6 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
BDA96EE7161785350736DA01B10270D2

About this manual

This guide explains photovoltaic module construction, string and array protection, and how to select fuse links for PV installations. It covers fuse selection criteria, worked examples, and an overview of Bussmann series solar fuse links and holders.

The guide states that Eaton Bussmann series PV fuse links are designed for IEC 60269-6 gPV protection, operate at 1.35 x In, and meet UL 2579. It also describes temperature derating for string fuse links and altitude derating above 2000 metres.

What's inside

  • Eaton's Bussmann series solar technology solution
  • Introduction
  • IEC 60269-6 gPV standard
  • Photovoltaic module Construction
  • String protection Overview
  • How to select fuse links for string protection
  • Array Protection Overview
  • How to select fuse links for array protection
  • Solar fuse links overview
  • Index

Specifications

PV fuse link operation1.35 x In
String fuse voltage rating>= 1.20 x Voc x Ns
String fuse current rating>= 1.56 x Isc
Altitude derating0.5% per 100 m above 2000 m

Frequently asked questions

When is string protection required in a PV system?

PV systems with three or more strings connected in parallel need to have each string protected.

What voltage rating should a string fuse link have?

The fuse link voltage rating should be at least 1.20 x Voc x Ns.

What current rating should a string fuse link have?

The fuse link current rating should be at least 1.56 x Isc.

How does altitude affect PV fuse current capability?

Above 2000 metres sea level, every 100 metre increase derates the fuse current by 0.5%.