This manual introduces Eaton's Bussmann series solar technology solution and how to select the appropriate fuse links and combiner box to provide comprehensive protection for solar systems.
This is the Eaton Bussmann series photovoltaic application guide. It addresses overcurrent and overvoltage protection for solar PV systems and presents Bussmann series PV fuse links, fuse holders, fuse blocks, surge protection devices and combiner boxes.
The guide covers the IEC 60269-6 gPV standard, PV module construction and output, string and array protection, fuse-link selection factors and worked examples. It then gives product sections for 10 x 38 mm, 14 x 51 mm, 14 x 65 mm, NH style, flush end and XL style PV fuse links, SPDs and combiner boxes.
| Fuse link utilisation class | gPV |
|---|---|
| IEC standard | IEC 60269-6 |
| Operating current for IEC 60269-6 gPV | 1.35 x In |
| UL standard | UL 2579 |
When three or more strings are connected in parallel, each string needs a fuse link to protect cables and modules from overcurrent faults. Systems with fewer than three strings do not generate enough current to damage the modules in a fault, provided conductors are sized correctly.
IEC 60269-6 defines specific characteristics that a fuse link must meet to protect PV systems, using utilisation class gPV. Eaton's Bussmann series PV fuse links are designed to meet this standard.
For more than three parallel strings, the fuse link voltage rating should be at least 1.20 x Voc x Ns and the current rating at least 1.56 x Isc. The selected fuse must also satisfy derating, the module maximum overcurrent protection rating and the string cable rating.
A module using 6-inch cells can achieve approximately 8 A maximum power point current per module, with a typical voltage output of around 30 V.