This manual describes the type LDD-301-DI4-OP-S258 photoelectric distance sensor. The sensor is manufactured by Radionic and meets IECEx and ATEX certification standards. It is suitable for use in Ex zones (0), 1, and 2 and has a maximum measurement range of 250 mm to 282 mm. The sensor also features high measurement accuracy, a visible red light laser, and a stainless steel 1.4404 housing.
This document is the original operating manual for the Matrix LDD-301-DI4-OP-S258 photoelectric distance sensor, a time-of-flight sensor certified for use in explosive atmospheres. It provides technical data, electrical connection details, installation prescriptions, function description, and safety information.
The sensor provides an analog 4 mA to 20 mA current output and an RS-485 serial interface, with a START input for measurement control. The manual also covers maintenance, laser safety, conformity declarations, and mechanical dimensions.
| Measuring method | Time-of-flight measuring |
|---|---|
| Measurement range, analog output | 250 mm to 282 mm |
| Ex protection | Gas, II 2(1)G Ex d [op is Ga] IIA T3 Gb |
| Ex zones | Zones (0), 1, 2 |
| Maximum optical radiant intensity | <=1 mW, 620 nm to 690 nm |
| Maximum optical radiant power | <=5 mW/mm2 |
| Light source | Laser Class 2 per EN 60825-1 |
| Response time | 0.25 s to 4.5 s |
| Power-up delay time | 800 ms |
| Supply voltage | 24 VDC +/-10% |
| Maximum permissible voltage | 30 VDC |
| Current consumption | 70 mA |
| Maximum power dissipation | 2.4 W |
| Typical measurement tolerance | +/-1 mm up to 10 m |
| Maximum measurement tolerance | +/-2 mm up to 10 m |
| Distance-dependent tolerance increase | <=0.15 mm/m |
| Analog current output | PNP, 4 mA to 20 mA, short-circuit protected |
| Analog output range | 250 mm to 282 mm (250 mm = 4 mA, 282 mm = 20 mA) |
| Analog error indication | 3.5 mA means invalid measurement |
| Analog output resolution | 1 mm = 0.5 mA |
| Analog load range | 500 ohm <= RL <= 1000 ohm |
| Serial interface | RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, no handshaking |
| Serial interface range | 50 mm to 30 m |
| Serial interface resolution | 1 mm |
| START input | PNP compatible; H +24 VDC starts measurement, L 0 V stops measurement |
| Housing | M42, stainless steel 1.4404 |
| Enclosure rating | IP67 |
| Ambient operating temperature | -10 C to +35 C |
| Storage temperature | -20 C to +70 C |
| Relative humidity | 15% to 80% |
| Connection cable | 5 m, PUR jacket, 6+PE x 0.5 mm2, shielded |
| Accessories | 2 nuts M42 |
| Options | Cable length up to 100 m on request |
The analog output covers 250 mm to 282 mm.
It indicates that no valid measurement could be achieved.
Apply +24 VDC to the START input to start measurement; connect it to 0 V to stop measurement.
The RS-485 interface uses 9600 baud, 8 data bits, 1 stop bit, no parity, and no handshaking.