ABB low-voltage AC drive PIHF harmonic filter user manual, suitable for ACS510/ACS530 ACx580-01/04 ACS880-01/04. Introduce product overview, installation and maintenance safety, filter installation and debugging instructions and other content.
This ABB user manual covers the PIHF harmonic filter used with low-voltage AC drives such as ACS510/ACS530, ACx580-01/04 and ACS880-01/04. It describes the filter's operating principle, safety instructions, mechanical installation, electrical connection and model information.
The manual also provides technical data, parameter settings for matching drives, cooling and installation clearances, and service and training contact information. This manual is written in Chinese.
| Rated voltage | Three-phase, 380-415 V, +10% / -15% |
|---|---|
| Protection rating | IP00 |
| Harmonic filtering effect | THDI < 10% at full load |
| Frequency | 50 Hz |
| Overvoltage category | Category III (EN 61800-5-1) |
| Overheat protection | 155 C |
| Cooling method | Air cooling |
| Ambient temperature (operating) | -25 C to +40 C at full load |
| Storage temperature | -25 C to +70 C |
| Operating altitude | 0 to 2000 m |
| Relative humidity | 0 to 95%, non-condensing |
| Cooling clearance | At least 150 mm around the filter |
| Parallel filter spacing | At least 200 mm between filters |
| Capacitor environment temperature | Below 50 C |
| Recommended filter-to-drive cable length | Not more than 10 m |
It is a low-pass filter that suppresses high-frequency harmonic currents on the drive input side.
It is a drive accessory filter and may only be installed at the drive power input.
Yes, one PIHF can supply multiple drives if their total load does not exceed the filter rated power.
Keep at least 150 mm of cooling space around the filter.