This document mainly introduces the installation, electrical connection, debugging, maintenance and troubleshooting methods of SUN2000-55KTL-HV-D1, SUN2000-55KTL-IN-HV-D1, SUN2000- 55KTL-HV-D1-001, SUN2000-60KTL-HV-D1 and SUN2000-60KTL-HV-D1-001 (hereinafter referred to as SUN2000).
This is the Chinese user manual (document version 06, dated 2020-01-03) for the Huawei SUN2000 series three-phase string PV grid-tied inverters SUN2000-55KTL-HV-D1, SUN2000-55KTL-IN-HV-D1, SUN2000-55KTL-HV-D1-001, SUN2000-60KTL-HV-D1 and SUN2000-60KTL-HV-D1-001. Its stated main function is to convert the DC power produced by PV strings into AC power and feed it into the grid.
The manual is addressed to PV plant operators and qualified electrical technicians and covers safety precautions, product introduction, inverter storage, system installation, electrical connection (grounding, AC output, DC input and RS485 communication), system commissioning and power-off procedures, human-machine interaction through a USB drive and the SUN2000 app, system maintenance and fault handling, inverter disposal, technical data and grid standard codes. This manual is written in Chinese.
| Left installation clearance | ≥ 200 mm |
|---|---|
| Right installation clearance | ≥ 300 mm |
| Top installation clearance | ≥ 500 mm |
| Bottom installation clearance | ≥ 600 mm |
| Front installation clearance | ≥ 1000 mm |
| Heatsink temperature during operation | May exceed 60 ºC |
| Wait time after power-off before work | At least 5 minutes |
| DC input connector | Amphenol UTX PV connector |
It is a three-phase string PV grid-tied inverter that converts the DC power produced by PV strings into AC power and feeds it into the grid.
Only professional electrical technicians who have read the manual and are familiar with electrical system safety standards.
At least 5 minutes after the SUN2000 is powered off.
Use the Amphenol UTX PV connectors supplied with the inverter; damage caused by incompatible connectors is not covered by warranty.