The AMVAC breaker is a magnetically actuated and latched breaker capable of a high number of operations due to its simplified design. Fully compliant with IEEE Standards C37.04, C37.06 and C37.09, the AMVAC breaker is a great fit for many applications.
The AMVAC breaker is a magnetically actuated, latched circuit breaker designed for high operational endurance and compliance with IEEE standards. It features a maintenance-free magnetic actuator, embedded vacuum interrupters, and on-board capacitors to eliminate battery draw. The guide details ratings by voltage class (5, 15, 27 kV), mechanical endurance (10,000 operations), timing (≤83 ms total interrupt time), and physical dimensions. It also covers power requirements and auxiliary switch ratings for control voltages up to 240 Vac.
| Voltage Class | 5 kV, 15 kV, 27 kV |
|---|---|
| Continuous Current | 1200 A, 2000 A, 3000 A |
| Short Circuit Current | 25 kA, 40 kA, 50 kA |
| Mechanical Endurance | 10,000 operations |
| Height | 28 in |
| Weight | 334 lb |
| Actuator Driver Power | 10 W (standby), 100 W (capacitor charging) |
| Auxiliary Contact Voltage | 24 Vdc, 48 Vdc, 125 Vdc, 250 Vdc, 120 Vac, 240 Vac |
The AMVAC breaker has short circuit current ratings of 25 kA, 40 kA, and 50 kA depending on voltage class.
The AMVAC breaker has a mechanical endurance rating of 10,000 operations.
The actuator driver requires 10 W for standby and 100 W for capacitor charging.