This manual introduces the configuration, operation and features of ABB medium voltage soft starters
This manual provides installation and maintenance instructions for ABB’s SSM medium voltage soft starters, designed for AC motors from 200 to 7,500 HP. It details configuration, operation, and features including overload protection, phase imbalance detection, and programmable ramp settings. The unit includes a disconnect switch, fuses, contactors, and SCR modules for motor control and protection. Optional 'soft start only' versions are available for retrofit applications.
The manual covers technical specifications such as voltage ratings (2300–7200 VAC), SCR configurations (6, 12, or 18 SCRs), cooling, ambient conditions, and control options including Modbus RTU and RS-485 communication. It also explains safety interlocks, transient voltage protection, and programmable fault displays for diagnostics.
| AC Supply Voltage | 2300, 3300, 4160, 7200 VAC +10% to -15% |
|---|---|
| Nominal HP Ratings | 2300V 200 HP - 2500HP; 3300V 200HP - 3000HP; 4160V 250HP - 5000HP; 6000/7200V 300HP - 7500HP |
| SCR Peak Inverse Voltage Ratings | 6500V - 21000V (model dependent) |
| Ambient Condition | 0° to 50°C (32° to 122°F) for chassis units; 0° to 40°C (32° to 104°F) for enclosed units |
| Control Voltage | 120VAC (customer supplied) |
| BIL Rating | 2300V - 7200V 60KV; 11000 - 15000V 110KV |
It supports 2300, 3300, 4160, and 7200 VAC with a tolerance of +10% to -15%.
Vacuum contactors are included for both in-line isolation and SCR bypass, rated up to 7.2 kV for 6000-7200V units.
It has 125% continuous overload capacity and up to 600% for 30 seconds.