Flagro FVN/P-200 Indirect Fired Space Heaters Operating Instructions Manual

This manual describes how to safely use unmanned gas space heaters.


Flagro FVN/P-200 Indirect Fired Space Heaters Operating Instructions Manual - cover page
Brand
Flagro
Category
Heater
Document type
User Manual
Language
English
Pages
17
File format
PDF
File size
1.2 MB
Published
26 October, 2023
Updated
26 October, 2023
Model
P-200
MD5 checksum
0FDC71445030DBA549C70D70D1E83982

About this manual

This operating instructions manual from Flagro Industries Limited covers the FVN/P-200 indirect fired space heater. The heater is approved as a construction heater under ANSI Z83.7/CSA 2.14 2000 and certified for use in Canada and the U.S.A.; the specifications list FVP-200 propane and FVN-200 natural gas versions, 200,000 btuh input, and 1500 cfm air circulation.

The manual covers installation, cylinder connection and piping, pressure and fuel requirements, electrical supply, venting requirements, clearance to combustibles, maintenance, start-up and shutdown, troubleshooting if the heater fails to start, safe operation precautions, and combustion air adjustments with a burner set-up chart.

What's inside

  • Specifications
  • Installation
  • Connecting the Cylinder
  • Electrical
  • Venting Requirements
  • Clearance to Combustibles
  • Maintenance
  • Start Up Instructions
  • To Shut Down
  • Combustion Air Adjustments

Specifications

ModelFVP-200 propane; FVN-200 natural gas
Input200,000 btuh
FuelPropane or natural gas
Manifold pressure3.5 in. W.C. propane; 3.5 in. W.C. natural gas
Maximum inlet pressure13.0 in. W.C. propane; 10.0 in. W.C. natural gas
IgnitionDirect spark ignition; thermostat control
Air circulation1500 cfm
Fuel consumption9.25 lbs/hr propane; 190 cfh natural gas
Clearance to combustiblesTop 3 ft; front 10 ft; sides 1 ft; rear 2 ft; flue pipe 3 ft
Electrical supply115 V
Current requirement15 A
Weight280 lbs

Frequently asked questions

What fuel can the FVN/P-200 use?

It will operate on propane or natural gas, but not both; the rating plate determines which fuel to use.

How much fresh air ventilation is required?

The instructions require 1 sq. in. of fresh air for every 1000 BTUH of heat.

What should I check if the heater fails to start?

Press the manual reset button at the rear of the burner, then check gas pressure supply and the power supply and extension cord.

What is the maximum horizontal vent run?

The maximum horizontal run is 30 ft.

Download PDF (1.2 MB)