Instructions manual for FVNP-200RC indirect fired space heaters.
The FLAGRO FVNP-200RC is a dual-fuel indirect fired space heater rated at 200,000 btuh and intended primarily for temporary heating of buildings under construction, alteration, repair, or emergencies. It is certified for use in Canada and the U.S.A. under ANSI Z83.7/CSA 2.14 2000 and is cETLus listed.
The operating instructions cover installation by a qualified gas technician, clearance to combustibles, electrical supply and grounding, cylinder connection, piping and pressure requirements, fuel selection, power indicator light meanings, flue pipe venting, ducting, maintenance, and start-up. The heater uses propane or natural gas, and the fuel selector valve must be set to the proper fuel position.
| Model | FVNP-200RC |
|---|---|
| Input range | 200,000 btuh |
| Fuel | Propane and natural gas |
| Manifold pressure | 1.45 in. W.C. propane; 3.44 in. W.C. natural gas |
| Maximum inlet pressure | 13 in. W.C. propane; 10 in. W.C. natural gas |
| Electrical | 115V 15 AMP (6 AMP draw) |
| Ignition | Direct Spark Ignition |
| Air circulation | 2600 cfm |
| Fuel consumption | 9.25 lbs/hr propane; 190 cfh natural gas |
| Vent outlet diameter | 6 in. |
It operates on propane and natural gas; the manual describes it as a dual fuel unit.
It requires 115V, 15 AMP service, with a 6 AMP draw.
At least 10 ft (3 m).
13.0 in. W.C. for propane and 10.0 in. W.C. for natural gas.