This is an operating instructions manual that details how to use the FVO-400RC indirect fired space heater. It is certified for use in Canada and the United States.
The FVO-400RC is an indirect fired space heater from Flagro Industries Limited, certified for use in Canada and the U.S.A. as a construction heater under CSA B140.8 and UL 733. The manual covers specifications, installation, clearances to combustibles, fuel and electrical requirements, flue pipe and ducting, maintenance, start-up and shutdown.
It describes start-up in manual or thermostat mode, what to check if the heater fails to start, safe operation precautions, and combustion air adjustment using a certified combustion analyzer and smoke tester.
| Model | FVO-400RC |
|---|---|
| Input range | 325,000 – 390,000 |
| Fuel | No.1, No. 2, diesel or kerosene |
| Fuel pressure | 170 psi |
| Nozzle | 2.25 x 45B |
| Electrical | 120V 15AMP |
| Ignition | Direct Spark |
| Air circulation | 4000 cfm |
| Fuel consumption | 2.75 Gal/hr |
| Approval | cETLus listed |
The heater will operate with No.1, No.2, diesel or kerosene. For temperatures below -10°C (8°F), No.1 fuel oil or kerosene must be used.
There must be 2-4 gallons of fuel in the tank for the heater to start properly.
The heater requires 15 amps for proper operation and must be plugged into a properly grounded three-prong receptacle. Use 12/3 AWG cord at 50 feet or 10/3 AWG at 100 feet.
Press the manual reset button at the rear of the burner, check fuel level, make sure there are no air locks in the fuel lines or filter, verify the power supply and extension cord, and check the fuel filter and burner nozzle.