This is a user manual for the 301EM gas detection device.
The Honeywell 301EM is a gas detection device designed for monitoring specific gases such as refrigerants (R11, R12, R13B1, etc.) and toxic or combustible gases. The manual covers the intended use, unpacking, and detailed installation guidelines, including wall mounting and determining the number of transmitters required for the system.
| Power | 22-27 Vac, 50/60 Hz; 29-38Vdc, 2 A@ 29 Vdc |
|---|---|
| Standard Outputs | 4 DPDT relays; 3 Outputs at 24 Vdc @ 250 mA each |
| Communication | RS-485: Modbus or Vulbus |
| Audible Alarm | 65 dBA @ 1 m (3 ft) |
| Operating Temperature Range | 0 to 40°C (32°F to 100°F) |
| Operating Humidity Range | 0 to 95% RH (non-condensing) |
| Size (HxWxD) | 20.3 x 28 x 7 cm |
| Weight | 1.02 kg (2.26 lbs) |
| Gases Detected (301IRFS) | R11, R12, R13B1, R22, R114, R123, R125, R134a, R227, R245A, R404A, R407C, R410A, R507, R508b |
| Sensing Technology (301IRFS) | Infrared sensor |
| Measurement Range (301IRFS) | 0-1000 ppm |
| Accuracy (301IRFS) | ±10ppm à 50 ppm / ±40ppm à 500 ppm |
The operating temperature range is 0 to 40°C (32°F to 100°F).
The unit supports RS-485 communication using Modbus or Vulbus protocols.
It detects R11, R12, R13B1, R22, R114, R123, R125, R134a, R227, R245A, R404A, R407C, R410A, R507, and R508b.
The measurement range is 0-1000 ppm.