Honeywell Searchline Excel Open Path Infrared Gas Detector Installation Guide

This guide provides the installation personnel with the basic information necessary to mechanically install the Searchline Excel system units and make the necessary electrical connections. This guide is not intended to replace the associated Searchline Excel Technical Handbook (2104M0505) which contains the full safety, installation, commissioning, maintenance and fault finding instructions. These procedures assume that consideration of the location and mounting of the system units has already been taken into account in accordance with the guidelines in the Technical Handbook. The following diagram shows a typical system configuratio


Honeywell Searchline Excel Open Path Infrared Gas Detector Installation Guide - cover page
Brand
Honeywell
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
385 KB
Published
21 October, 2023
Updated
21 October, 2023
MD5 checksum
13173F9FAA4363126D15630E1D8F8753

About this manual

This guide provides step-by-step instructions for installing the Honeywell Searchline Excel Open Path Infrared Gas Detector, including mechanical assembly and electrical connections. It covers safety precautions, mounting options, and wiring standards to ensure proper installation in hazardous areas. The guide assumes prior consideration of location and mounting per the Technical Handbook and includes diagrams for system configuration and component mounting.

Key sections include safety guidelines, mechanical assembly for transmitter and receiver units, and detailed electrical installation procedures with specific requirements for cabling, grounding, and compliance with international standards such as EN50081 & EN50082.

What's inside

  • Introduction
  • Safety
  • Mechanical Assembly
  • Installation
  • Electrical Installation
  • Receiver Connections via DVC100
  • Receiver Connections via DX100
  • Transmitter Connections
  • Remote Installation Receiver Connections
  • Transmitter Connections - Turbo Heating Disabled

Frequently asked questions

What is the maximum round loop impedance for a nominal 24V system supply?

The maximum round loop impedance is 14 ohms.

What is the minimum supply voltage applied to the system at a current of 420mA?

The minimum supply voltage applied to the system is 18V.

What is the maximum peak voltage allowed between the unit case earth and any field cable conductor?

The maximum peak voltage must be less than 350V.