This manual describes the operation and maintenance of the TD series low voltage digital solid state starter.
The TD Series is a digitally programmable solid state reduced voltage soft starter designed for three-phase AC induction motors. It features a six-SCR design with voltage/current ramp control and anti-oscillation circuits to ensure smooth load acceleration. The unit includes programmable keypad settings for starting torque, ramp time, current limit, and decel control, along with solid state electronic overload protection.
| HP Ratings | 48 - 1250 HP |
|---|---|
| Unit Overload Capacity | 125% - Continuous |
| Cooling Method | Convection up to 180A, fan assisted 62 - 120A, Fan ventilated 220 - 1250A |
| Ambient Condition Design | 0° to 50 °C (32° to 122°F) |
The factory setting is 0, which corresponds to Manual mode where the operator must press the Reset key before restarting.
The SCRs are sized to withstand starting currents of 500% for 60 seconds.
Chassis units operate in temperatures from 0° to 50 °C (32° to 122°F).
The factory setting for the overload reset is 0, which corresponds to Manual mode.