4400 series battery cabinet installation and operation manual
This manual provides instructions for the safety, storage, installation, operation, and maintenance of Toshiba Top Terminal Battery Cabinets. These systems are shipped partially assembled with internal pre-wiring and standard over-current breaker protection. They are built and tested to UL 1778 standards and are designed to provide DC backup power for UPS applications.
| Voltage (UPS Application) | 288 VDC Nominal |
|---|---|
| Breaker Type | Standard |
| Battery Type | Valve Regulated Lead Acid (VRLA), sealed, non-spillable |
| Battery Voltage | 6 or 12 Volt DC Nominal |
| Cabinet Width (15-30kVA) | 36.0 inches |
| Cabinet Height (15-30kVA) | 65.1 inches |
| Cabinet Weight (Empty, 15-30kVA) | 515 lbs |
The cabinets use Valve Regulated Lead Acid (VRLA), sealed, non-spillable batteries with a top terminal design.
The nominal voltage for the UPS application is 288 VDC.
The 15-30kVA cabinet measures 36.0 inches wide, 29.5 inches deep, and 65.1 inches high.