This document is the user manual of Eaton Automation AG XNE-1SWIRE
The Eaton XNE-1SWIRE is a decentralized I/O component designed to integrate into XI/ON stations on industrial networks such as CANopen, PROFIBUS-DP, and DeviceNet. It functions as a local module within an XN-PLC-CANopen station or as a remote module connected via an XN-GWBR-CANopen gateway.
The document details the product's features, including its ability to scan physical structures and store them in the module, activate PLC configuration checks, and manage diagnostics. It provides instructions for integrating the module into various network protocols, configuring it using MXpro software, and understanding its technical specifications regarding power supply, current consumption, and environmental requirements.
| Nominal voltage from supply terminal | 24 V DC (18 to 30 V DC) |
|---|---|
| Nominal current consumption from module bus | max. 60 mA |
| Supply current SWIRE (SWIRE bus at full load) | max. 600 mA |
| Number of XNE-1SWIRE modules per XI/ON station | max. 3 |
| Ambient temperature operating | 0 to +55 °C |
The device integrates as a local I/O component in XN-PLC-CANopen and as a decentralized component on CANopen, Profibus, and DeviceNet networks.
The system supports a maximum of 16 SWIRE slaves per bus.
A maximum of 3 XNE-1SWIRE modules are allowed per XI/ON station.