The Eaton XNE-1SWIRE is a decentralized I/O component designed to integrate into XI/ON stations on industrial networks such as CANopen, PROFIBUS-DP, and DeviceNet. It functions as a local module within an XN-PLC-CANopen station or as a remote module connected via an XN-GWBR-CANopen gateway.

The document details the product's features, including its ability to scan physical structures and store them in the module, activate PLC configuration checks, and manage diagnostics. It provides instructions for integrating the module into various network protocols, configuring it using MXpro software, and understanding its technical specifications regarding power supply, current consumption, and environmental requirements.

What's inside

  • General
  • Product description
  • Integration of the module in PROFIBUS-DP
  • Integration of the module in Device Net
  • Integration of the module in CANopen
  • Moeller SWIRE conformance criteria
  • Configuration with MXpro

Specifications

Nominal voltage from supply terminal24 V DC (18 to 30 V DC)
Nominal current consumption from module busmax. 60 mA
Supply current SWIRE (SWIRE bus at full load)max. 600 mA
Number of XNE-1SWIRE modules per XI/ON stationmax. 3
Ambient temperature operating0 to +55 °C

Frequently asked questions

What networks can the XNE-1SWIRE integrate into?

The device integrates as a local I/O component in XN-PLC-CANopen and as a decentralized component on CANopen, Profibus, and DeviceNet networks.

What is the maximum number of SWIRE slaves per bus?

The system supports a maximum of 16 SWIRE slaves per bus.

How many XNE-1SWIRE modules can be used per station?

A maximum of 3 XNE-1SWIRE modules are allowed per XI/ON station.