This document provides instructions for using the AMDP-□/C811 series motor protectors from Shenyang Xinwei Automation Co., Ltd. It includes product features, protection functions, application range, and model specifications.
This document is the user manual for the XWAM AMDP-□/C811 series motor protector, manufactured by Shenyang Xinwei Automation Co., Ltd. The device is designed for three-phase AC motors with a rated voltage not exceeding 1140V and a frequency of 50Hz or 60Hz. It features a DSP core for digital setting and display, offering comprehensive protection functions including phase loss, short circuit, ground fault, stall, overload, current imbalance, and zero-sequence current detection. This manual is written in Chinese.
| Rated Voltage | Not exceeding 1140V |
|---|---|
| Frequency | 50Hz or 60Hz |
| Working Voltage | AC 85V — 265V, DC 85V — 265V |
| Power Consumption | Less than 2W |
| Operating Temperature | -20℃ — 50℃ |
| Relay Contact | 1 NO, AC 250V/10A (resistive load), DC 30V/10A |
| DO/DI Voltage | DC 24V±10% |
| DO Drive Capability | Max 100mA per channel |
| Zero-Sequence Current Input Impedance | Less than 1 Ω |
It provides protection against phase loss, short circuit, ground fault, stall, overload, current imbalance, and zero-sequence current.
After clearing the fault, press the reset button R or apply a clear fault pulse signal to DI1 to clear the fault state.
Fault code EE01 indicates a ground fault.
The M key is the storage key; pressing it saves the current parameter and calls up the next or previous parameter.