XWAM AMDP-□/C811 Series Motor Protector User Manual

This document provides instructions for using the AMDP-□/C811 series motor protectors from Shenyang Xinwei Automation Co., Ltd. It includes product features, protection functions, application range, and model specifications.


XWAM AMDP-□/C811 Series Motor Protector User Manual - cover page
Brand
XWAM
Category
Motor
Document type
User Manual
Language
Chinese
Pages
12
File format
PDF
File size
479 KB
Published
13 September, 2022
Updated
28 September, 2023
Model
C811
MD5 checksum
49FF96D6CC35F88C9F4B9990BB7036F1

About this manual

This document is the user manual for the XWAM AMDP-□/C811 series motor protector, manufactured by Shenyang Xinwei Automation Co., Ltd. The device is designed for three-phase AC motors with a rated voltage not exceeding 1140V and a frequency of 50Hz or 60Hz. It features a DSP core for digital setting and display, offering comprehensive protection functions including phase loss, short circuit, ground fault, stall, overload, current imbalance, and zero-sequence current detection. This manual is written in Chinese.

What's inside

  • Product Overview
  • Protection Functions
  • Applicable Scope
  • Working Process
  • LED Display
  • Keyboard Operation
  • Zero-Sequence Current Protection
  • 4-20mA Output
  • Fault Codes
  • Parameter Settings

Specifications

Rated VoltageNot exceeding 1140V
Frequency50Hz or 60Hz
Working VoltageAC 85V — 265V, DC 85V — 265V
Power ConsumptionLess than 2W
Operating Temperature-20℃ — 50℃
Relay Contact1 NO, AC 250V/10A (resistive load), DC 30V/10A
DO/DI VoltageDC 24V±10%
DO Drive CapabilityMax 100mA per channel
Zero-Sequence Current Input ImpedanceLess than 1 Ω

Frequently asked questions

What protection functions does the AMDP-□/C811 series provide?

It provides protection against phase loss, short circuit, ground fault, stall, overload, current imbalance, and zero-sequence current.

How is the motor protector reset after a fault?

After clearing the fault, press the reset button R or apply a clear fault pulse signal to DI1 to clear the fault state.

What does fault code EE01 indicate?

Fault code EE01 indicates a ground fault.

What is the function of the M key on the keypad?

The M key is the storage key; pressing it saves the current parameter and calls up the next or previous parameter.

Download PDF (479 KB)