Honeywell TF428WNM/U Networked Thermostat User Manual

This document introduces the application scope and main features of the TF428WNM/U networked thermostat, including the control of three-speed fans and valve switches, as well as the ability to integrate with building automation systems. The thermostat also features timed shutdown, timed cycling, and random startup functions for precise room temperature control and energy savings.


Honeywell TF428WNM/U Networked Thermostat User Manual - cover page
Brand
Honeywell
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
1.1 MB
Updated
27 September, 2023
MD5 checksum
1870DFCA3D663D5715A52EEA9475793A

About this manual

The Honeywell TF428WNM/U is a networked thermostat designed for fan coil unit systems. It controls three-speed fans and valve switching using the Modbus RTU protocol, allowing for easy integration with building automation systems. The device supports various modes including two-pipe and four-pipe systems, ventilation, and manual or automatic fan speed control. Key features include scheduled shutdown, scheduled cycling, and random start functions to optimize energy efficiency and temperature control. This manual is written in Chinese.

What's inside

  • Application Scope
  • Technical Specifications
  • Functions
  • Ventilation Mode
  • Overcooling Protection
  • Installation
  • Terminal Definitions
  • Local Settings
  • Modbus Address Table

Specifications

Communication ProtocolRS485 Modbus RTU
Baud Rate4800/9600/19200
Operating Voltage220/230 VAC; 50/60Hz
Control Accuracy±1°C at 21°C
Fan Load Capacity (Resistive)4A
Valve Load Capacity (Resistive)2A
Operating Temperature Range0 ~ 49°C
Temperature Setting Range10 ~ 32°C

Frequently asked questions

What communication protocol does the TF428WNM/U use?

The thermostat uses the RS485 Modbus RTU protocol for communication.

Can the thermostat be used in four-pipe systems?

Yes, the TF428WNM/U supports four-pipe systems with manual or automatic regulation of heating and cooling.

What is the default baud rate for the device?

The default baud rate is 9600, though it can be set to 4800 or 19200.

How does the overcooling protection function work?

When enabled, the thermostat starts heating if the indoor temperature drops below 6°C while the unit is off, until it reaches 8°C.