Toshiba VF-AS1 Error Ekn1: F4:2 tuning error

Toshiba VF-AS1 inverter · taken from the manufacturer’s manual, pages cited

Error codeEkn1

Ekn1 indicates an F4:2 tuning error where tuning required to boost torque as specified with F4:2 cannot be performed, the capacity of the motor connected is 2 notches or more smaller than the inverter capacity, or the motor connected is not a three-phase inductive motor. The manual's first action is: “Make sure that a motor is connected. Make sure that the motor is at standstill. Perform auto-tuning 1 again and if the error persists, perform tuning manually.”

Model
Toshiba VF-AS1
Display shows
F4:2 tuning error (Ekn1)
Type
Error code
Source
Manual p. 297

What Ekn1 means

F4:2 tuning error p. 297

Common causes

  • Tuning required to boost torque as specified with F4:2 cannot be performed. The capacity of the motor connected is 2 notches or more smaller than the inverter capacity. The motor connected is not a three-phase inductive motor. Tuning is performed while no motor is connected. The cables connecting the inverter to the motor are too long, they are more than 30m in length. Tuning is performed while the motor is running. p. 297

What to do

  1. Make sure that a motor is connected. Make sure that the motor is at standstill. Perform auto-tuning 1 again and if the error persists, perform tuning manually. p. 297

Before you service the product, read the safety instructions in the manual p. 17.

If Ekn1 is still not resolved

  • Read the Instruction Manual p. 17
    “Read the Instruction Manual.”

This page summarises what the manufacturer’s manual says about Ekn1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.