Siemens G120C Error F30659: SI P2: Write request for parameter rejected

Siemens G120C drive · taken from the manufacturer’s manual, pages cited

Fault codeF30659

A write request to one or more Safety Integrated parameters on processor 2 was rejected during parameterization or configuration, without triggering a safety stop. The manual's first action is: “OFF2”

Model
Siemens G120C
Display shows
SI P2: Write request for parameter rejected (F30659)
Type
Fault code
Source
Manual p. 747

What F30659 means

SI P2: Write request for parameter rejected p. 747

Common causes

  • Error in the parameterization / configuration / commissioning procedure (18) p. 747
  • The write request for one or several Safety Integrated parameters on processor 2 was rejected. p. 747
  • This fault does not result in a safety stop response. p. 747
  • Fault value (r0949, interpret decimal): p. 747
  • 10: An attempt was made to enable the STO function although this cannot be supported. p. 747
  • 15: An attempt was made to enable the motion monitoring functions integrated in the drive although these cannot be supported. p. 747
  • 16: An attempt was made to enable the PROFIsafe communications although this cannot be supported. p. 747
  • 18: An attempt was made to enable the PROFIsafe function for Basic Functions although this cannot be supported. p. 747
  • 20: An attempt was made to simultaneously enable both the drive-integrated motion monitoring functions via integrated F-DI and STO via terminals, even though these cannot be supported at the same time. p. 747
  • 28: An attempt was made to enable the "STO via terminals at the Power Module" function although this cannot be supported. p. 747
  • See also: r9771 (SI common functions (processor 1)), r9871 (SI common functions (processor 2)) p. 747
  • For fault value = 10, 15, 16, 18: p. 747
  • For fault value = 28: p. 747
  • Note: p. 747
  • F-DI: Failsafe Digital Input p. 747
  • STO: Safe Torque Off p. 747

What to do

  1. OFF2 p. 747
  2. - check whether there are faults in the safety function alignment (F01655, F30655) and if required, carry out diagnostics for the faults involved. p. 747
  3. - use a Control Unit that supports the required function. p. 747

Before you service the product, read the safety instructions in the manual p. 4.

If F30659 is still not resolved

  • contact service / dealer p. 4
    “Warning concept This Manual contains information which you must observe to ensure your own personal safety as well as to avoid material damage.”
  • contact service / dealer p. 12
    “WARNING Danger to life if the safety instructions and residual risks are not observed”

This page summarises what the manufacturer’s manual says about F30659; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.