Fault codeF30655
Processor 1 and processor 2 were unable to align their Safety Integrated monitoring functions due to communication errors or incompatible configurations. The manual lists no action for this code.
- Model
- Siemens G120C
- Display shows
- SI P2: Align monitoring functions (F30655)
- Type
- Fault code
- Source
- Manual p. 746
What F30655 means
SI P2: Align monitoring functions p. 746
Common causes
- An error has occurred when aligning the Safety Integrated monitoring functions on processor 1 and processor 2. No common set of supported SI monitoring functions was able to be determined. p. 746
- - there is a communication error between processor 1 and processor 2 or communication has failed. p. 746
- This fault results in a STOP A that cannot be acknowledged. p. 746
- Fault value (r0949, interpret hexadecimal): p. 746
- Only for internal Siemens troubleshooting. p. 746
- - carry out a POWER ON (switch-off/switch-on). p. 746
- - check the electrical cabinet design and cable routing for EMC compliance p. 746
If F30655 is still not resolved
This page summarises what the manufacturer’s manual says about F30655; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.