Fault codeF30650
Processor 2 of the drive’s Safety Integrated function requires an acceptance test to verify its operational integrity before resuming operation. The manual lists no action for this code.
- Model
- Siemens G120C
- Display shows
- SI P2: Acceptance test required (F30650)
- Type
- Fault code
- Source
- Manual p. 745
What F30650 means
SI P2: Acceptance test required p. 745
Common causes
- The drive-integrated "Safety Integrated" function on processor 2 requires an acceptance test. p. 745
- This fault results in a STOP A that can be acknowledged. p. 745
- Fault value (r0949, interpret decimal): p. 745
- 130: Safety parameters for processor 2 not available. p. 745
- Note: p. 745
- This fault value is always output when Safety Integrated is commissioned for the first time. p. 745
- 1000: Reference and actual checksum on processor 2 are not identical (booting). p. 745
- - at least one checksum-checked piece of data is defective. p. 745
- - safety parameters set offline and loaded into the Control Unit. p. 745
- 2000: Reference and actual checksum on processor 2 are not identical (commissioning mode). p. 745
- 2003: Acceptance test is required as a safety parameter has been changed. p. 745
- 2010: Enable of safety-related brake control between the two monitoring channels differ (p9602 not equal to p9802). p. 745
- 9999: Subsequent response of another safety-related fault that occurred when booting that requires an acceptance test. p. 745
If F30650 is still not resolved
This page summarises what the manufacturer’s manual says about F30650; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.