Fault codeF30600
Processor 2 of the drive’s Safety Integrated function has initiated a STOP A because it detected an error in its safety signal path or failed to respond to fault F30611. The manual's first action is: “0: Stop request from processor 1.”
- Model
- Siemens G120C
- Display shows
- SI P2: STOP A initiated (F30600)
- Type
- Fault code
- Source
- Manual p. 743
What F30600 means
SI P2: STOP A initiated p. 743
Common causes
- The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A. p. 743
- - forced checking procedure (test stop) of the safety switch-off signal path on processor 2 unsuccessful. p. 743
- - subsequent response to fault F30611 (defect in a monitoring channel). p. 743
- Fault value (r0949, interpret decimal): p. 743
- 1005: Pulses suppressed although STO not selected and there is no internal STOP A present. p. 743
- 1010: Pulses enabled although STO is selected or an internal STOP A is present. p. 743
- 1011: Internal fault for the pulse enable in the Power Module. p. 743
- Remedy: p. 743
- For fault value = 9999: p. 743
- Note: p. 743
- STO: Safe Torque Off p. 743
What to do
- 0: Stop request from processor 1. p. 743
- 9999: Subsequent response to fault F30611. p. 743
- - select Safe Torque Off and de-select again. p. 743
- - carry out a POWER ON (switch-off/switch-on) for all components. p. 743
- - replace Power Module involved. p. 743
- - carry out diagnostics for fault F30611. p. 743
- PM: Power Module p. 743
Before you service the product, read the safety instructions in the manual p. 4.
If F30600 is still not resolved
This page summarises what the manufacturer’s manual says about F30600; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.