Fault codeF01662
An internal communication error occurred within a module on the Siemens G120C, requiring a power cycle to resolve. The manual's first action is: “- carry out a POWER ON (switch-off/switch-on).”
- Model
- Siemens G120C
- Display shows
- Error internal communications (F01662)
- Type
- Fault code
- Source
- Manual p. 686
What F01662 means
Error internal communications p. 686
Common causes
- A module-internal communication error has occurred. p. 686
- Fault value (r0949, interpret hexadecimal): p. 686
What to do
- - carry out a POWER ON (switch-off/switch-on). p. 686
- - check the electrical cabinet design and cable routing for EMC compliance. p. 686
- - check whether an impermissible voltage is connected at one of the digital outputs. p. 686
- - check whether a digital output is loaded with an impermissible current. p. 686
- - upgrade firmware to later version. p. 686
- - contact Technical Support. p. 686
Before you service the product, read the safety instructions in the manual p. 4.
If F01662 is still not resolved
This page summarises what the manufacturer’s manual says about F01662; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.