Voltage measurements are not providing plausible values, indicating a possible wiring or parameterization issue. The manual's first action is: “- Deactivate voltage measurement (p0247.0 = 0). - Deactivate flying restart with voltage measurement (p0247.5 = 0) and deactivate fast flying restart (p1780.11 = 0).”
- Model
- Siemens G120C
- Display shows
- Voltage measured values not plausible (A05065)
- Type
- Fault code
- Source
- Manual p. 697
What A05065 means
Voltage measured values not plausible p. 697
Common causes
- The voltage measurement does not supply any plausible values and is not used. p. 697
- Alarm value (r2124, interpret bitwise binary): Bit 1: Phase U Bit 2: Phase V Bit 3: Phase W p. 697
- The following parameterization must be made in order to deactivate the alarm: p. 697
What to do
- - Deactivate voltage measurement (p0247.0 = 0). - Deactivate flying restart with voltage measurement (p0247.5 = 0) and deactivate fast flying restart (p1780.11 = 0). p. 697
Before you service the product, read the safety instructions in the manual p. 4.
If A05065 is still not resolved
This page summarises what the manufacturer’s manual says about A05065; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.