Siemens G120C Error F06310: Supply voltage (p0210) incorrectly parameterized

Siemens G120C drive · taken from the manufacturer’s manual, pages cited

Fault codeF06310

The measured DC voltage is outside the tolerance range after precharging, requiring drive shutdown to acknowledge the fault. The manual lists no action for this code.

Model
Siemens G120C
Display shows
Supply voltage (p0210) incorrectly parameterized (F06310)
Type
Fault code
Source
Manual p. 697

What F06310 means

Supply voltage (p0210) incorrectly parameterized p. 697

Common causes

  • The measured DC voltage lies outside the tolerance range after precharging has been completed. p. 697
  • Permissible range: 1.16 * p0210 < r0070 < 1.6 * p0210 p. 697
  • Note: The fault can only be acknowledged when the drive is switched off. p. 697
  • See also: p0210 (Drive unit line supply voltage) p. 697

If F06310 is still not resolved

  • contact service / dealer p. 4
    “Warning concept This Manual contains information which you must observe to ensure your own personal safety as well as to avoid material damage.”
  • contact service / dealer p. 12
    “WARNING Danger to life if the safety instructions and residual risks are not observed”

This page summarises what the manufacturer’s manual says about F06310; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.