The motor temperature has exceeded its alarm threshold, triggering a response based on parameterized settings. The manual's first action is: “PTC or bimetallic NC contact: The response threshold of 1650 Ohm was exceeded or the NC contact opened and the timer (p0606) has expired. The response parameterized in p0610 becomes active.”
- Model
- Siemens G120C
- Display shows
- Drive: Motor overtemperature (F07011)
- Type
- Alarm code
- Source
- Manual p. 698
What F07011 means
Drive: Motor overtemperature p. 698
Common causes
- The motor temperature has exceeded the fault threshold (p0605) or the timer (p0606) after the alarm threshold was exceeded (p0604) has expired. The response parameterized in p0610 becomes active. The alarm is withdrawn if the response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm). p. 698
- Possible causes: p. 698
- Fault value (r0949, interpret decimal): p. 698
What to do
- PTC or bimetallic NC contact: The response threshold of 1650 Ohm was exceeded or the NC contact opened and the timer (p0606) has expired. The response parameterized in p0610 becomes active. p. 698
- - motor is overloaded. - motor ambient temperature too high. - wire breakage or sensor not connected. p. 698
- 200: Motor temperature model 1 (12b): temperature too high. See also: p0604, p0605, p0606, p0612, p0625, p0626, p0627, p0628 p. 698
- - reduce the motor load. p. 698
- - check the ambient temperature and the motor ventilation. p. 698
- - check the wiring and the connection of the PTC or bimetallic NC contact. p. 698
Before you service the product, read the safety instructions in the manual p. 4.
If F07011 is still not resolved
This page summarises what the manufacturer’s manual says about F07011; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.