Siemens CU240S Error F00061: Par Cl. MMC-PS not fitted Fault

Siemens CU240S · taken from the manufacturer’s manual, pages cited

Fault codeF00061

Par Cl. MMC-PS not fitted Fault means the MMC-PS is not connected or incorrect type, or cannot write to MMC. The manual lists no action for this code.

Model
Siemens CU240S
Display shows
Par Cl. MMC-PS not fitted Fault (F00061)
Type
Fault code
Source
Manual p. 387

What F00061 means

Par Cl. MMC-PS not fitted Fault p. 387

Common causes

  • r0949 = 0: MMC-PS Not Connected or incorrect MMC-PS Type p. 387
  • r0949 = 1: MMC-PS cannot write to MMC p. 387
  • r0949 = 2: MMC-PS File not available p. 387
  • r0949 = 3: MMC-PS cannot read the file p. 387
  • r0949 = 4: MMC-PS problems in the clone File ( e.g CRC ) p. 387
  • r0949 = 0: Use MMC-PS with FAT12 or FAT16 format or correct MMC-PS Type, or fit an MMC-PS to Drive. p. 387
  • r0949 = 1: Check MMC ( e.g is MMC full ) - Format MMC again to FAT16 p. 387
  • r0949 = 2: Put the correct named file in the correct directory /USER/SINAMICS/DATA. p. 387
  • r0949 = 3: Make sure File is accessible. Recreate File if possible p. 387
  • r0949 = 4: File has been changed - Recreate File p. 387

If F00061 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F00061; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.