Fault codeF00061
Par Cl. MMC-PS not fitted Fault means the MMC-PS is not connected or incorrect type, or cannot write to MMC. The manual lists no action for this code.
- Model
- Siemens CU240S
- Display shows
- Par Cl. MMC-PS not fitted Fault (F00061)
- Type
- Fault code
- Source
- Manual p. 387
What F00061 means
Par Cl. MMC-PS not fitted Fault p. 387
Common causes
- r0949 = 0: MMC-PS Not Connected or incorrect MMC-PS Type p. 387
- r0949 = 1: MMC-PS cannot write to MMC p. 387
- r0949 = 2: MMC-PS File not available p. 387
- r0949 = 3: MMC-PS cannot read the file p. 387
- r0949 = 4: MMC-PS problems in the clone File ( e.g CRC ) p. 387
- r0949 = 0: Use MMC-PS with FAT12 or FAT16 format or correct MMC-PS Type, or fit an MMC-PS to Drive. p. 387
- r0949 = 1: Check MMC ( e.g is MMC full ) - Format MMC again to FAT16 p. 387
- r0949 = 2: Put the correct named file in the correct directory /USER/SINAMICS/DATA. p. 387
- r0949 = 3: Make sure File is accessible. Recreate File if possible p. 387
- r0949 = 4: File has been changed - Recreate File p. 387
If F00061 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00061; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.