Fault codeF00060
Asic Timeout indicates internal communications failure, possibly due to hardware or software link failures. The manual's first action is: “Check connection between inverter power module and inverter control unit”
- Model
- Siemens CU240S
- Display shows
- Asic Timeout (F00060)
- Type
- Fault code
- Source
- Manual p. 386
What F00060 means
Asic Timeout p. 386
Common causes
- Internal communications failure p. 386
- r0949 = 0: HW reported Link Fail p. 386
- r0949 = 1: SW reported Link Fail p. 386
- Communication failure due to EMC problems p. 386
- Use EMC filter p. 386
- Fault appears sporadically. p. 386
- Fault appears immediately when mains voltage is applied and an ON command is given. p. 386
What to do
- Check connection between inverter power module and inverter control unit p. 386
- Check - and if necessary - improve EMC p. 386
- If fault persists, change inverter. p. 386
- Contact Service Department. p. 386
If F00060 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00060; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.