Fault codeF00070
PLC setpoint fault means no setpoint values are received from PLC during telegram off time. The manual's first action is: “Check and improve - if necessary - the value in p2040”
- Model
- Siemens CU240S
- Display shows
- PLC setpoint fault (F00070)
- Type
- Fault code
- Source
- Manual p. 387
What F00070 means
PLC setpoint fault p. 387
Common causes
- No setpoint values from PLC during telegram off time p. 387
What to do
- Check and improve - if necessary - the value in p2040 p. 387
- Acknowledge fault p. 387
- If fault persists, change inverter control unit p. 387
If F00070 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F00070; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.