Siemens CU240S Error F00055: BOP-EEPROM Fault

Siemens CU240S · taken from the manufacturer’s manual, pages cited

Fault codeF00055

BOP-EEPROM Fault means read or write failure while saving non-volatile parameters to EEPROM on BOP during parameter cloning. The manual's first action is: “Factory Reset and new parameterization”

Model
Siemens CU240S
Display shows
BOP-EEPROM Fault (F00055)
Type
Fault code
Source
Manual p. 386

What F00055 means

BOP-EEPROM Fault p. 386

Common causes

  • Read or write failure while saving non-volatile parameter to EEPROM on BOP whilst parameter cloning. p. 386
  • r0949 = 5096 p. 386
  • r0949 = 9160 p. 386
  • r0949 = 1000 + Block No: Reading data block failed p. 386
  • r0949 = 3000 + Block No: Reading data block failed p. 386
  • r0949 = 4000 + Block No: Writing data block failed p. 386
  • r0949 = 5098: BOP EEPROM too Small p. 386
  • r0949 = 6000 + Block No: writing data block verify failed p. 386
  • r0949 = 7000 + Block No: Reading data block at wrong time p. 386
  • r0949 = 8000 + Block No: writing data block at wrong time p. 386
  • r0949 = 9160: Drive EEPROM too Small p. 386

What to do

  1. Factory Reset and new parameterization p. 386
  2. Change BOP p. 386
  3. Use a BOP with a bigger EEPROM p. 386
  4. Use a BOP with a smaller EEPROM p. 386

If F00055 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F00055; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.