Siemens CU240B/E-2 Error F30022: Power unit: Monitoring U_ce

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF30022

The monitoring of the collector-emitter voltage (U_ce) of the semiconductor in the power unit has responded. The manual's first action is: “Acknowledge: POWER ON”

Model
Siemens CU240B/E-2
Display shows
Power unit: Monitoring U_ce (F30022)
Type
Fault code
Source
Manual p. 714

What F30022 means

Power unit: Monitoring U_ce p. 714

Common causes

  • Reaction: OFF2 p. 714
  • In the power unit, the monitoring of the collector-emitter voltage (U_ce) of the semiconductor has responded. p. 714
  • Possible causes: p. 714
  • - power supply of the IGBT gating module missing. p. 714
  • - short-circuit at the power unit output. p. 714
  • - defective semiconductor in the power unit. p. 714
  • Fault value (r0949, interpret binary): p. 714
  • Bit 0: Short-circuit in phase U p. 714
  • Bit 1: Short-circuit in phase V p. 714
  • Bit 2: Short-circuit in phase W p. 714
  • Bit 3: Light transmitter enable defective p. 714
  • Bit 4: U_ce group fault signal interrupted p. 714
  • See also: r0949 (Fault value) p. 714
  • Remedy: p. 714
  • - check the power supply of the IGBT gating module (24 V). p. 714
  • - check the power cable connections. p. 714
  • - select the defective semiconductor and replace. p. 714

What to do

  1. Acknowledge: POWER ON p. 714
  2. - fiber-optic cable interrupted. p. 714
  3. - check the fiber-optic cable and if required, replace. p. 714

If F30022 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F30022; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.