Siemens CU240B/E-2 Error F30025: Power unit: Chip overtemperature

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF30025

The power unit has detected chip overtemperature because the permissible load duty cycle was not maintained. The manual's first action is: “Acknowledge: IMMEDIATELY”

Model
Siemens CU240B/E-2
Display shows
Power unit: Chip overtemperature (F30025)
Type
Fault code
Source
Manual p. 714

What F30025 means

Power unit: Chip overtemperature p. 714

Common causes

  • Reaction: OFF2 p. 714
  • Cause: p. 714
  • - The permissible load duty cycle was not maintained. p. 714
  • - insufficient cooling, fan failure. p. 714
  • - overload. p. 714
  • - ambient temperature too high. p. 714
  • - pulse frequency too high. p. 714
  • Fault value (r0949): p. 714
  • Temperature difference between the heat sink and chip [1 Bit = 0.01 °C]. p. 714
  • Remedy: p. 714
  • - check whether the fan is running. p. 714
  • - check the fan elements. p. 714
  • - check whether the ambient temperature is in the permissible range. p. 714
  • - check the motor load. p. 714
  • - reduce the pulse frequency if this is higher than the rated pulse frequency. p. 714
  • Notice: p. 714
  • See also: r0037 (Power unit temperatures) p. 714

What to do

  1. Acknowledge: IMMEDIATELY p. 714
  2. - Chip temperature of the semiconductor has exceeded the permissible limit value. p. 714
  3. - adapt the load duty cycle. p. 714
  4. This fault can only be acknowledged after this alarm threshold for alarm A05001 has been undershot. p. 714

If F30025 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F30025; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.