Siemens CU240B/E-2 Error F07082: Macro: Execution not possible

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF07082

The macro cannot be executed due to an error. The manual lists no action for this code.

Model
Siemens CU240B/E-2
Display shows
Macro: Execution not possible (F07082)
Type
Fault code
Source
Manual p. 691

What F07082 means

Macro: Execution not possible p. 691

Common causes

  • The macro cannot be executed. p. 691
  • Fault value (r0949, interpret hexadecimal): p. 691
  • occc = preliminary parameter number, bb = supplementary information, aa = fault cause p. 691
  • Fault causes for the trigger parameter itself: p. 691
  • 19: Called file is not valid for the trigger parameter. p. 691
  • 20: Called file is not valid for parameter 15. p. 691
  • 21: Called file is not valid for parameter 700. p. 691
  • 22: Called file is not valid for parameter 1000. p. 691
  • 23: Called file is not valid for parameter 1500. p. 691
  • 24: Data type of a TAG is incorrect (e.g. Index, number or bit is not U16). p. 691
  • Fault causes for the parameters to be set: p. 691
  • 25: Error level has an undefined value. p. 691
  • 26: Mode has an undefined value. p. 691
  • 27: A value was entered as string in the tag value that is not "DEFAULT". p. 691
  • 31: Entered drive object type unknown. p. 691
  • 32: A device was not able to be found for the determined drive object number. p. 691
  • 34: A trigger parameter was recursively called. p. 691
  • 35: It is not permissible to write to the parameter via macro. p. 691
  • 36: Check, writing to a parameter unsuccessful, parameter can only be read, not available, incorrect data type, value range or assignment incorrect. p. 691
  • 37: Source parameter for a BICO interconnection was not able to be determined. p. 691
  • 38: An index was set for a non-indexed (or CDS-dependent) parameter. p. 691
  • 39: No index was set for an indexed parameter. p. 691
  • 41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN. p. 691
  • 42: A value not equal to 0 or 1 was set for a BitOperation. p. 691
  • 43: Reading the parameter to be changed by the BitOperation was unsuccessful. p. 691
  • 51: Factory setting for DEVICE may only be executed on the DEVICE. p. 691
  • 61: The setting of a value was unsuccessful. p. 691

If F07082 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F07082; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.