Fault codeF30024
The power unit has detected overtemperature due to exceeding the permissible load duty cycle. The manual's first action is: “Acknowledge: IMMEDIATELY”
- Model
- Siemens CU240B/E-2
- Display shows
- Power unit: Overtemperature thermal model (F30024)
- Type
- Fault code
- Source
- Manual p. 714
What F30024 means
Power unit: Overtemperature thermal model p. 714
Common causes
- Reaction: OFF2 p. 714
- Cause: p. 714
- - The permissible load duty cycle was not maintained. p. 714
- - insufficient cooling, fan failure. p. 714
- - overload. p. 714
- - ambient temperature too high. p. 714
- - pulse frequency too high. p. 714
- See also: r0037 (Power unit temperatures) p. 714
- Remedy: p. 714
- - check whether the fan is running. p. 714
- - check the fan elements. p. 714
- - check whether the ambient temperature is in the permissible range. p. 714
- - check the motor load. p. 714
- - reduce the pulse frequency if this is higher than the rated pulse frequency. p. 714
- - if DC braking is active: reduce braking current (p1232). p. 714
What to do
- Acknowledge: IMMEDIATELY p. 714
- - The temperature difference between the heat sink and chip has exceeded the permissible limit value. p. 714
- - adapt the load duty cycle. p. 714
If F30024 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F30024; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.