Fault codeF07011
The motor temperature has exceeded the fault threshold or timer after the alarm threshold was exceeded. The manual lists no action for this code.
- Model
- Siemens CU240B/E-2
- Display shows
- Drive: Motor overtemperature (F07011)
- Type
- Fault code
- Source
- Manual p. 690
What F07011 means
Drive: Motor overtemperature p. 690
Common causes
- The motor temperature has exceeded the fault threshold (p0605) or the timer (p0606) after the alarm threshold was exceeded (p0604) has expired. The response parameterized in p0610 becomes active. The alarm is withdrawn if the response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm). p. 690
- PTC or bimetallic NC contact: p. 690
- The response threshold of 1650 Ohm was exceeded or the NC contact opened and the timer (p0606) has expired. The response parameterized in p0610 becomes active. p. 690
If F07011 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F07011; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.