Siemens CU240B/E-2 Error F07011: Drive: Motor overtemperature

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF07011

The motor temperature has exceeded the fault threshold or timer after the alarm threshold was exceeded. The manual lists no action for this code.

Model
Siemens CU240B/E-2
Display shows
Drive: Motor overtemperature (F07011)
Type
Fault code
Source
Manual p. 690

What F07011 means

Drive: Motor overtemperature p. 690

Common causes

  • The motor temperature has exceeded the fault threshold (p0605) or the timer (p0606) after the alarm threshold was exceeded (p0604) has expired. The response parameterized in p0610 becomes active. The alarm is withdrawn if the response threshold for wire breakage or sensor not connected is exceeded (R > 2120 Ohm). p. 690
  • PTC or bimetallic NC contact: p. 690
  • The response threshold of 1650 Ohm was exceeded or the NC contact opened and the timer (p0606) has expired. The response parameterized in p0610 becomes active. p. 690

If F07011 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F07011; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.