There is a PROFIBUS configuration error for using Safety Integrated monitoring functions with a higher-level control. The manual's first action is: “check and, if necessary, correct the PROFIBUS configuration of the safety slot on the master side.”
- Model
- Siemens CU240B/E-2
- Display shows
- SI P1: PROFIBUS configuration error (F01653)
- Type
- Fault code
- Source
- Manual p. 673
What F01653 means
SI P1: PROFIBUS configuration error p. 673
Common causes
- There is a PROFIBUS configuration error for using Safety Integrated monitoring functions with a higher-level control. p. 673
- For safety functions that have been enabled, this fault results in a STOP A that cannot be acknowledged. p. 673
- Note: Fault value (r0949, decimal interpretation): p. 673
- 200: A safety slot for receive data from the control has not been configured. p. 673
- 210, 220: The configured safety slot for the receive data from the control has an unknown format. p. 673
- 230: The configured safety slot for the receive data from the F-PLC has the incorrect length. p. 673
- 250: A PROFIsafe slot is configured in the higher-level F control, however PROFiSafe is not enabled in the drive. p. 673
- 300: A safety slot for the send data to the control has not been configured. p. 673
- 310, 320: The configured safety slot for the send data to the control has an unknown format. p. 673
- 330: The configured safety slot for the send data to the F-PLC has the incorrect length. p. 673
- 331: The configured safety slot for the send data to the F-PLC has the incorrect length. p. 673
- The following generally applies: p. 673
- - upgrade the Control Unit software. p. 673
- For fault value = 250: p. 673
- Re fault value = 231, 331: p. 673
- The following applies for p9501.30 = 1 (F-DI via PROFiSafe is enabled): PROFiSafe telegram 900 must be configured. p. 673
- The following applies for p9501.30 = 0 (F-DI via PROFiSafe is not enabled): PROFiSafe telegram 30 must be configured. p. 673
What to do
- check and, if necessary, correct the PROFIBUS configuration of the safety slot on the master side. p. 673
- remove the PROFiSafe configuring in the higher-level F control or enable PROFiSafe in the drive. p. 673
- configure the PROFiSafe telegram matching the parameterization in the F-PLC. p. 673
If F01653 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about F01653; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.
