Siemens CU240B/E-2 Error F03505: CU: Analog input wire breakage

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF03505

The input current of the analog input has undershot the threshold value parameterized in p0761[...3]. The manual's first action is: “Check the connection to the signal source for interruptions. Check the magnitude of the injected current - it is possible that the inefed signal is too low. The input current measured by the analog input can be read in r0752[X].”

Model
Siemens CU240B/E-2
Display shows
CU: Analog input wire breakage (F03505)
Type
Fault code
Source
Manual p. 688

What F03505 means

CU: Analog input wire breakage p. 688

Common causes

  • The input current of the analog input has undershot the threshold value parameterized in p0761[...3]. This fault only occurs when p0756[0...1] = 1 (2 ... 10 V with monitoring) or p0756[0...2] = 3 (4 ... 20 mA with monitoring) is set. p. 688

What to do

  1. Check the connection to the signal source for interruptions. Check the magnitude of the injected current - it is possible that the inefed signal is too low. The input current measured by the analog input can be read in r0752[X]. p. 688

If F03505 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F03505; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.