Siemens CU240B/E-2 Error F07016: Drive: Motor temperature sensor fault

Control unit · taken from the manufacturer’s manual, pages cited

Fault codeF07016

An error was detected when evaluating the temperature sensor set in p0601, indicating wire breakage or sensor not connected. The manual lists no action for this code.

Model
Siemens CU240B/E-2
Display shows
Drive: Motor temperature sensor fault (F07016)
Type
Fault code
Source
Manual p. 691

What F07016 means

Drive: Motor temperature sensor fault p. 691

Common causes

  • An error was detected when evaluating the temperature sensor set in p0601. p. 691
  • - wire breakage or sensor not connected (KTY: R > 2120 Ohm). p. 691
  • - measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm). p. 691

If F07016 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.

This page summarises what the manufacturer’s manual says about F07016; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.