Fault codeE-20
[Torque Boost Too High] means control board CPU is not operational, EEPROM power supply is incompatible, or product hardware detection fault. The manual's first action is: “Contact Schneider Electric service for inverter repair.”
- Model
- Schneider Electric ATV212
- Display shows
- [Torque Boost Too High] (E-20)
- Type
- Fault code
- Source
- Manual p. 153
What E-20 means
[Torque Boost Too High] p. 153
Common causes
- Control board CPU is not operational. p. 153
- EEPROM power supply is incompatible. p. 153
- Product hardware detection fault. p. 153
- Data write error occurred. p. 153
- Inverter power loss during parameter reset caused a data write error. p. 153
- Data read error occurred. p. 153
- Motor or motor cable has a grounding fault. p. 153
- One or more output phases are missing. p. 153
- One input phase is missing. p. 153
- Parameters F202, F203, F210, or F212 are set incorrectly. p. 153
- Control board RAM is not operational. p. 153
- Control board ROM is not operational. p. 153
- Control board CPU cannot operate. p. 153
- Serial communication error. p. 153
- One motor current sensor is not operational. p. 153
- Network communication error. p. 153
- Graphics display option cable is disconnected. p. 153
- Parameters F401 through F494 are set incorrectly. p. 153
- Motor is too large for the inverter. p. 153
- Motor cable size is too small. p. 153
- Motor is still rotating when auto‑tuning starts. p. 153
- The inverter is not driving a three‑phase induction motor. p. 153
- Main control board cannot operate. p. 153
- If this does not clear the error, the inverter should be replaced. p. 153
- Check FL relay connections (FLA/FLB). p. 153
- Fan valve remains open or is welded. p. 153
- Check relay configuration (F130/F132). p. 153
What to do
- Contact Schneider Electric service for inverter repair. p. 153
- Power cycle to clear the fault. p. 153
- Power cycle to clear the fault and retry the parameter reset operation. p. 153
- If the fault does not clear, contact Schneider Electric service for inverter repair. p. 153
- Check the motor and motor cable for grounding faults. p. 153
- Determine the cause of output phase loss (e.g., poor connection, output open circuit, or motor winding open) and correct the issue. p. 153
- Determine the cause of input phase loss and correct it. p. 153
- Set the parameters to the correct values. p. 153
- Contact Schneider Electric service for inverter repair. p. 153
- Check network control devices and cables. p. 153
- Replace the inverter. p. 153
- Check the RJ45 cable. p. 153
- Correctly set parameters F401‑F494. p. 153
- Use an inverter with a larger specification. p. 153
- Use a motor cable with a larger specification. p. 153
- Confirm the motor is stopped before starting auto‑tuning. p. 153
- Use the inverter only with three‑phase induction motors. p. 153
- Set parameter [Parameter Reset] (tYP) to 6. p. 153
- Set [Fan Valve Fault Management] (F583) to 0. p. 153
- Check relay configuration (F130/F132). p. 153
- Set [Fan Valve Feedback Type] (F583) to 0 or 1. Check FL relay connections (FLA/FLB). p. 153
Before you service the product, read the safety instructions in the manual p. 5.
If E-20 is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about E-20; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.