Schneider Electric ATV212 Error DC1: [Overcurrent During Acceleration]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeDC1

[Overcurrent During Acceleration] means acceleration time is too short, parameter [Motor Control Mode] (P1) is set incorrectly, or inverter is starting a rotating load. The manual's first action is: “Increase the acceleration time parameter (RCC or F500).”

Model
Schneider Electric ATV212
Display shows
[Overcurrent During Acceleration] (DC1)
Type
Fault code
Source
Manual p. 154

What DC1 means

[Overcurrent During Acceleration] p. 154

Common causes

  • Acceleration time is too short. p. 154
  • Parameter [Motor Control Mode] (P1) is set incorrectly. p. 154
  • Inverter is starting a rotating load. p. 154
  • Inverter is powering a low‑impedance motor. p. 154
  • Ground fault. p. 154

What to do

  1. Increase the acceleration time parameter (RCC or F500). p. 154
  2. Select the correct setting value for parameter [Motor Control Mode] (P1). p. 154
  3. Enable flywheel start, parameter F301. p. 154
  4. Adjust the switching frequency parameter F300. p. 154
  5. Set parameter F316 to 1 or 3. p. 154

Before you service the product, read the safety instructions in the manual p. 5.

If DC1 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about DC1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.