[CPU Communication Error] means torque boost parameter [Automatic Torque Boost] (F402) is set too high, motor impedance is too low, or during deceleration, when [Motor Control Mode] (P1) = (1) [Variable Torque], any of the following three conditions occur: – Stop process – Load current value > 88% × [Motor Current Limiting] (F501) – The manual's first action is: “Repeat the inverter auto‑tuning, then lower the [Automatic Torque Boost] (F402) parameter.”
- Model
- Schneider Electric ATV212
- Display shows
- [CPU Communication Error] (E-19)
- Type
- Error code
- Source
- Manual p. 153
What E-19 means
[CPU Communication Error] p. 153
Common causes
- Torque boost parameter [Automatic Torque Boost] (F402) is set too high. p. 153
- Motor impedance is too low. p. 153
- During deceleration, when [Motor Control Mode] (P1) = (1) [Variable Torque], any of the following three conditions occur: – Stop process – Load current value > 88% × [Motor Current Limiting] (F501) – Deceleration is too slow such that [Maximum Frequency] (FH) / [Deceleration Time 1] (dEC) × 2 ms < 0.01 Hz. p. 153
What to do
- Repeat the inverter auto‑tuning, then lower the [Automatic Torque Boost] (F402) parameter. p. 153
- Set [Automatic Acc/Dec Ramp] (AU1) = 0 (Disabled). p. 153
- Reduce the deceleration slope using [Deceleration Time 2] (F501) and [Acc/Dec Style Switch Frequency] (F505). p. 153
Before you service the product, read the safety instructions in the manual p. 5.
If E-19 is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about E-19; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.