Schneider Electric ATV212 Error CF12: [Download Transfer Fault]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeCF12

[Download Transfer Fault] means invalid configuration, configuration loaded into the inverter via bus or communication network is inconsistent, or transfer using PC software failed due to differing ratings (e.g., uploading an ATV212***M3 configuration to an ATV212***M4). The manual's first action is: “Check the previously loaded configuration.”

Model
Schneider Electric ATV212
Display shows
[Download Transfer Fault] (CF12)
Type
Fault code
Source
Manual p. 153

What CF12 means

[Download Transfer Fault] p. 153

Common causes

  • Invalid configuration p. 153
  • Configuration loaded into the inverter via bus or communication network is inconsistent. p. 153
  • Transfer using PC software failed due to differing ratings (e.g., uploading an ATV212***M3 configuration to an ATV212***M4). p. 153
  • VIA analog signal is below the level set by parameter F633. p. 153
  • The download configuration transfer to the inverter was interrupted. p. 153

What to do

  1. Check the previously loaded configuration. p. 153
  2. To perform the download, deselect "Display communication error" (go to Tool / Environment options / Startup / Comm). p. 153
  3. Check the VIA signal and correct the cause of signal loss. p. 153
  4. Confirm that parameter F633 is set correctly. p. 153
  5. Set CF12. This fault code remains even after the inverter is powered down. p. 153

Before you service the product, read the safety instructions in the manual p. 5.

If CF12 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about CF12; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.