Schneider Electric ATV212 Error DC2: [Overcurrent During Deceleration]

Schneider Electric ATV212 · taken from the manufacturer’s manual, pages cited

Fault codeDC2

[Overcurrent During Deceleration] means deceleration time is too short or ground fault. The manual's first action is: “Increase the deceleration time parameter (DEC or F501).”

Model
Schneider Electric ATV212
Display shows
[Overcurrent During Deceleration] (DC2)
Type
Fault code
Source
Manual p. 154

What DC2 means

[Overcurrent During Deceleration] p. 154

Common causes

  • Deceleration time is too short. p. 154
  • Ground fault. p. 154

What to do

  1. Increase the deceleration time parameter (DEC or F501). p. 154
  2. Set parameter F316 to 1 or 3. p. 154

Before you service the product, read the safety instructions in the manual p. 5.

If DC2 is still not resolved

  • 与当地的 Schneider Electric 代表联系 p. 7
    “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”

This page summarises what the manufacturer’s manual says about DC2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.