DNP3 10K events are enabled along with Recipe/Data Log in user program. The manual's first action is: “['Remove Recipe/Data Log configuration when DNP3 10K events bit (S:36/11) is set, then reload and Run.', 'OR', 'Clear DNP3 10K events bit (S:36/11) in the user program, then reload and Run.']”
- Model
- Rockwell Automation MicroLogix 1400
- Display shows
- INVALID DNP3 AND RPC/DLS CONFIGURATION (002A)
- Type
- Error code
- Source
- Manual p. 403
What 002A means
INVALID DNP3 AND RPC/DLS CONFIGURATION p. 403
Common causes
- DNP3 10K events are enabled along with Recipe/Data Log in user program. p. 403
What to do
- ['Remove Recipe/Data Log configuration when DNP3 10K events bit (S:36/11) is set, then reload and Run.', 'OR', 'Clear DNP3 10K events bit (S:36/11) in the user program, then reload and Run.'] p. 403
Before you service the product, read the safety instructions in the manual p. 274.
If 002A is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Rockwell Automation service.
This page summarises what the manufacturer’s manual says about 002A; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Rockwell Automation. Found a mistake? Report an error.