A fault routine number was entered in the status file, number (S:29), but either the fault routine was not physically created, or the fault routine number was less than 3 or greater than 255. The manual's first action is: “['Either clear the fault routine file number (S:29) in the status file, or create a fault routine for the file number reference in the status file (S:29). The file number must be greater than 2 and less than 255.']”
- Model
- Rockwell Automation MicroLogix 1400
- Display shows
- INVALID OR NONEXISTENT USER FAULT ROUTINE VALUE (0028)
- Type
- Error code
- Source
- Manual p. 403
What 0028 means
INVALID OR NONEXISTENT USER FAULT ROUTINE VALUE p. 403
Common causes
- A fault routine number was entered in the status file, number (S:29), but either the fault routine was not physically created, or the fault routine number was less than 3 or greater than 255. p. 403
What to do
- ['Either clear the fault routine file number (S:29) in the status file, or create a fault routine for the file number reference in the status file (S:29). The file number must be greater than 2 and less than 255.'] p. 403
Before you service the product, read the safety instructions in the manual p. 274.
If 0028 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Rockwell Automation service.
This page summarises what the manufacturer’s manual says about 0028; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Rockwell Automation. Found a mistake? Report an error.