Rockwell Automation MicroLogix 1400 Error 0028: INVALID OR NONEXISTENT USER FAULT ROUTINE VALUE

MicroLogix 1400 Programmable Controller · taken from the manufacturer’s manual, pages cited

Error code0028

A fault routine number was entered in the status file, number (S:29), but either the fault routine was not physically created, or the fault routine number was less than 3 or greater than 255. The manual's first action is: “['Either clear the fault routine file number (S:29) in the status file, or create a fault routine for the file number reference in the status file (S:29). The file number must be greater than 2 and less than 255.']”

Model
Rockwell Automation MicroLogix 1400
Display shows
INVALID OR NONEXISTENT USER FAULT ROUTINE VALUE (0028)
Type
Error code
Source
Manual p. 403

What 0028 means

INVALID OR NONEXISTENT USER FAULT ROUTINE VALUE p. 403

Common causes

  • A fault routine number was entered in the status file, number (S:29), but either the fault routine was not physically created, or the fault routine number was less than 3 or greater than 255. p. 403

What to do

  1. ['Either clear the fault routine file number (S:29) in the status file, or create a fault routine for the file number reference in the status file (S:29). The file number must be greater than 2 and less than 255.'] p. 403

Before you service the product, read the safety instructions in the manual p. 274.

If 0028 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Rockwell Automation service.

This page summarises what the manufacturer’s manual says about 0028; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Rockwell Automation. Found a mistake? Report an error.