Omron CS1W-LCB01 and CS1W-LCB05 Error 15: AT error

Omron CS1W-LCB01 and CS1W-LCB05 Loop Control Board · taken from the manufacturer’s manual, pages cited

Error code15

A limit cycle cannot be generated for Basic PID (Block Model 011) or Advanced PID (Block Model 012) or suitable PID constants cannot be calculated. The manual's first action is: “Execution of the relevant block will be stopped. Check the following AT parameters: ITEM 036 to ITEM 040. Also, set ITEM 051 to 2 s or less.”

Model
Omron CS1W-LCB01 and CS1W-LCB05
Display shows
AT error (15)
Type
Error code
Source
Manual p. 186

What 15 means

AT error p. 186

Common causes

  • A limit cycle cannot be generated for Basic PID (Block Model 011) or Advanced PID (Block Model 012) or suitable PID constants cannot be calculated. p. 186

What to do

  1. Execution of the relevant block will be stopped. Check the following AT parameters: ITEM 036 to ITEM 040. Also, set ITEM 051 to 2 s or less. p. 186

Before you service the product, read the safety instructions in the manual p. 11.

If 15 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.