A limit cycle cannot be generated for Basic PID (Block Model 011) or Advanced PID (Block Model 012) or suitable PID constants cannot be calculated. The manual's first action is: “Execution of the relevant block will be stopped. Check the following AT parameters: ITEM 036 to ITEM 040. Also, set ITEM 051 to 2 s or less.”
- Model
- Omron CS1W-LCB01 and CS1W-LCB05
- Display shows
- AT error (15)
- Type
- Error code
- Source
- Manual p. 186
What 15 means
AT error p. 186
Common causes
- A limit cycle cannot be generated for Basic PID (Block Model 011) or Advanced PID (Block Model 012) or suitable PID constants cannot be calculated. p. 186
What to do
- Execution of the relevant block will be stopped. Check the following AT parameters: ITEM 036 to ITEM 040. Also, set ITEM 051 to 2 s or less. p. 186
Before you service the product, read the safety instructions in the manual p. 11.
If 15 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about 15; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.